Function Blocks 
HMON High Monitor Function Block 
170    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
HMON High Monitor Function Block 
Description 
The HMON label stands for High Monitor. 
 
 
 
This block is part of the 
Alarm/Monitor category.  
Function 
Monitors two analog input values (X and Y) and turns ON a digital output if X exceeds Y. 
A hysteresis adjustment is provided to prevent output cycling. 
•  If X > Y, then OUT = ON. 
•  If X < or = (Y – Hysteresis), then OUT = OFF. 
•  If (Y – Hysteresis) < X < Y, then OUT = Previous State. 
Input 
X 
= Analog value. 
Y = Analog value 
Output 
OUT
 = Digital signal 
Block properties 
 
 
 
Double click on the function block to access the function block properties dialog box.