Function Blocks 
PDE Peer Data Exchange Function Block 
254    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
PDE Peer Data Exchange Function Block 
Description 
The PDE label stands for Peer Data Exchange.  
 
This block is part of the 
Communications categories. 
Function 
A communications function block that allows interconnecting controllers with Ethernet media and 
networking devices communicate with each other. 
It requires one block per controller; up to 32 controllers maximum. It supports up to  
8 Read and 4 Write parameters. 
The block does not support forcing, but will allow data writes to any if its inputs. 
Inputs 
EV1 through EV4
 - [ON] - data value written per scan 
WR1 through WR4 - Values to be written to the selected controller 
Attention: The block does not support bit packing and single bit writing. 
If the register is an integer type, the floating point input will be rounded up prior to the address register. 
Outputs 
RD1 through RD8
 - last read value from the selected controller. 
NO SCAN -   ON = device is not receiving updates from peer 
  OFF = device is receiving updates from peer 
NO CONN -  ON = cannot connect to peer device 
  OFF = Good connection, Peer found.