Function Blocks
SYNC Function Block
380 HC900 Hybrid Control Designer Function Block Reference Guide Revision 11
2/07
SYNC Function Block
Description
The SYNC label stands for Synchronize.
This block is part of the
Setpoint Program category.
Function
Used to synchronize the operation of two setpoint programs given the run. Hold and reset signals from each
program.
Input (available for logic control of programmer)
^RESET
= RESET command, when turned ON.
^HLD = HOLD command, when turned ON.
^RUN = RUN command, when turned ON.
^ADV = ADVANCE command, when turned ON
Output
The status of each programmer connected to the output pins of the block are monitored. A change in state
of any of the programmers is transferred to the other programmers. This occurs regardless of input pin
connections. Use of block inputs is optional.
ATTENTION
Ghold status is not transferred between programmers with this block.
Block properties
Double click on the function block to access the function block properties dialog box.

Table of Contents

Other manuals for Honeywell HC900

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HC900 and is the answer not in the manual?

Honeywell HC900 Specifications

General IconGeneral
SeriesHC900
RedundancyOptional
Programming LanguageFunction Block Diagram, Ladder Logic, Structured Text
InputsAnalog, Digital
OutputsAnalog, Digital, Relay
DisplayOptional
ControlPID, Advanced Control
Power Supply24V DC or 100-240V AC
Storage Temperature-40°C to 85°C
Humidity5% to 95% non-condensing
Communication ProtocolsModbus, Ethernet