EasyManua.ls Logo

Honeywell HC900 - Figure 114 TOT Function Block Examples

Honeywell HC900
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function Blocks
TOT Totalizer Function Block
Revision 11 HC900 Hybrid Control Designer Function Block Reference Guide 405
2/07
Example
HFigure 114 shows Function Block Diagrams using a TOT function block.
EXAMPLE 1
In UMC ON Delay timers are not retentive - if the RUN
input is logic 0, the timer is reset. A retentive timer has
an Enable and a Reset input. As long as the timer is
not reset, time will be accumulated when the Enable
Input is logic 1 (ON). This permits recording the time a
device such as a pump has been on.
This example uses a Totalizer function block as a
retentive timer. If a fixed input of 1 is provided to the
block using a Numeric Constant, the totalizer will time
up to 1 at the input rate selected (per sec, per min., per
hr, or per day). For example, if the “per hr” rate were
selected, the output would be 1.0 after 1 hour, 2.0 after
2 hours, etc, up to the Preset value.
A counter is shown to count the number of pump cycles
(On to OFF transitions).
The P4-RESET Digital Variable is used to reset the
timer and counter
EXAMPLE 2 - FLOW TOTALIZATION
Figure 114 TOT function block examples

Table of Contents

Other manuals for Honeywell HC900

Related product manuals