Function Blocks
SPS Setpoint Scheduler Function Block
356 HC900 Hybrid Control Designer Function Block Reference Guide Revision 11
2/07
MAIN OUTPUT LABELS tab
It lets you set up labels for Main Outputs in the Setpoint Schedule to be displayed on the Operator Interface. Enter
Label names, Units(eu), and Decimal places
HTable 103 describes the parameters and the value or selection.
Double click on the function block to access the function block properties dialog box.
Table 103 Main Output labels configuration parameters
Parameter Index # Parameter Description Value or Selection
SP
SP1 thru SP8
Label
N/A Label name for Operator Interface 8 characters max.
Units
N/A Units for Operator Interface 4 characters max.
Decimal
Places
N/A
Decimal places for operator
Interface
0 - 4