AGA3O Function Block
32 HC900 Hybrid Control Designer Function Block Reference Guide Revision 11
2/07
Properties Group Parameter Index # Parameter Description Value or Selection
will indicate the error and
the calculated outputs will
be set to 0.0
Flow Rates tab
Table 9 AGA3O Flow Rates tab configuration parameters
Properties Group Parameter Index # Parameter Description Value or Selection
QV Flow Rate Per Hour
Per Day
Defines the rate of time
for QV output flow.
Click Radio Button to select.
QV Multiplier Units Type (see
“UNITS” on
Orifice tab) =
US Metric
FT3/hr M3/ hr
Ft3/day M3/day
Provides a time period
other than “per hour” or
“per day”.
Enter Value
For example, if “per minute” is
desired, set the unit to “per
hour” and the multiplier to 1/60.
Default = 1.0.
QB Flow Rate Per Hour
Per Day
Defines the rate of time
for QB output flow.
Click Radio Button to select.
QB Multiplier Units Type (see
“UNITS” on
Orifice tab) =
US Metric
FT3/hr M3/ hr
Ft3/day M3/day
Provides a time period
other than “per hour” or
“per day”.
Enter Value
For example, if “per minute” is
desired, set the unit to “per
hour” and the multiplier to 1/60.
Default = 1.0.
QM Flow Rate Per Hour
Per Day
Defines the rate of time
for Qm output flow.
Click Radio Button to select.

Table of Contents