Function Blocks 
DEWP Function Block 
Revision 11    HC900 Hybrid Control Designer Function Block Reference Guide  135 
2/07     
CO Properties  %CO 
0 
Allows you to adjust % Carbon 
measurement to compensate 
for variations in the amount of 
CO in the carrier gas. 
2.0 to 35.0  
default = 20 
 
Use Actual % 
CO 
 
1 
Function block will use the 
actual % Carbon Monoxide 
that is defined through an 
analog input. 
Click on block to select. 
O2 Probe 
Manufacturer 
Carbon 
Probe 
Manufacturer 
N/A 
Select from Drop Down List of 
Manufacturers. 
•  Advanced Atmosphere 
Control Corp. 
•  Furnace Control Corp. 
•  Marathon Monitors 
•  Super Systems Inc. 
 
Example 
HFigure 29 shows a Function Block Diagram using a DEWP function block. This application uses the Dew 
Point function block to calculate dew point based on using a carbon probe.  A typical example might be for 
control of an endothermic atmosphere generator.  Alternatively, a Honeywell dew point transmitter could 
be used for a more direct measurement. 
 
 
 
Figure 29 DEWP function block example