Function Blocks 
RH Relative Humidity Function Block 
Revision 11    HC900 Hybrid Control Designer Function Block Reference Guide  321 
2/07     
Metric system 
Table 94  Metric units 
 
Metric ON OFF 
DRY °C °F 
WET °C °F 
PRES Pa PSI 
 
 
 
TIP 
It is physically impossible for the wet bulb to be warmer than the dry bulb. If this appears to be 
the case, it implies a problem with the sensors, and will result in a RH greater than 100 %.
 
Downstream blocks should detect that situation and react promptly. 
 
Example 
HFigure 85 shows an RH function block example.  
A setup parameter allows inputs to be in Degrees F or Degrees C.  When Degrees F is selected, pressure is 
assumed to be in PSIA.  When Degrees C is selected, pressure is assumed to be in Pa. (101325 Pa = 1 std. 
Atmosphere. 
 
 
 
Figure 85 RH function block example