Function Blocks
STSW Setpoint Scheduler State Switch Function Block
374 HC900 Hybrid Control Designer Function Block Reference Guide Revision 11
2/07
STSW Setpoint Scheduler State Switch Function Block
Description
The STSW label stands for the Setpoint Scheduler State Switch.
This block is part of the
Setpoint Scheduler category.
Function
Connects to Master block (SPS) via dedicated connection and accepts digital inputs to cause scheduler
mode changes. The State Switch block accepts state request digital inputs and produces an encoded output
for input to the master (SPS) block.
Inputs
^JOG
= OFF to ON requests JOG state
GHOLD = ON = guaranteed Hold State; ON to OFF and previous state was RUN, then return to RUN
mode.
^RESET = OFF to ON requests RESET state
^RUN = OFF to ON requests RUN state
^ADV = OFF to ON requests ADVANCE state
Outputs
STRQ
= for connection to the STQR input of the SPS function block. This block encodes discrete inputs to
a form that will convey change mode requests to the SPS block:
0.0 No Change
1.0 Jog State
2.0 Guaranteed Hold State
4.0 Reset State
8.0 Hold State
16.0 Run State
32.0 Advance state
Block properties
Double click on the function block to access the function block properties dialog box.
Example
HFigure 101 shows a Function Block Diagram (Setpoint Scheduler Suite) using a STSW function block.

Table of Contents

Other manuals for Honeywell HC900

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell HC900 and is the answer not in the manual?

Honeywell HC900 Specifications

General IconGeneral
SeriesHC900
RedundancyOptional
Programming LanguageFunction Block Diagram, Ladder Logic, Structured Text
InputsAnalog, Digital
OutputsAnalog, Digital, Relay
DisplayOptional
ControlPID, Advanced Control
Power Supply24V DC or 100-240V AC
Storage Temperature-40°C to 85°C
Humidity5% to 95% non-condensing
Communication ProtocolsModbus, Ethernet

Related product manuals