EasyManua.ls Logo

Honeywell HC900 - SPP Function Block

Honeywell HC900
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function Blocks
SPP Function Block
Revision 11 HC900 Hybrid Control Designer Function Block Reference Guide 343
2/07
SPP Function Block
Description
The SPP label stands for Setpoint Programmer.
This block is part of the
Setpoint Program category.
Function
Runs a setpoint ramp/soak program that produces a setpoint output on a time-based profile that is loaded
into the block. Up to 4 SPP blocks may be included in a system configuration. A single profile may be from
2 to 50 segments in length. Up to 70 profiles are stored in the controller’s memory.
Each segment of the
profile may be a ramp or soak except the last segment must be a soak.
In addition to the main ramp and soak output value, a second (AUX) analog value is available for each step
of the program. This output is a fixed soak value that may be used to provide a setpoint value for a
secondary control loop in the process. [For example, see
HExample 4 - Using the setpoint programmer AUX
output (page
H351).]
A Setpoint guarantee function is provided that holds the program if a process variable exceeds a predefined
deviation from setpoint. Selections allow setpoint guarantee to be active for the entire program, for soak
segments only, or for user specified segments, or for no segments. [For example, see
HExample 1 - PID with
setpoint programmer and guaranteed soak (page
H348).]
Up to 3 Process Variables may be configured as inputs to the block for setpoint guarantee.
Input
PV1
= Process Variable #1 value in engineering units, for deviation check.
PV2 = Process Variable #2 value in engineering units, for deviation check.

Table of Contents

Other manuals for Honeywell HC900

Related product manuals