Function Blocks 
LMON Low Monitor Function Block 
182    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
LMON Low Monitor Function Block 
Description 
The LMON label stands for Low Monitor.  
 
 
 
This block is part of the 
Alarm/Monitor category.  
Function 
Monitors two analog input values (X and Y), and turns ON a digital output if X is less than Y. 
A hysteresis adjustment is provided to prevent output cycling. 
•  If X < Y, then: OUT = ON. 
•  If X > or = (Y + Hysteresis), then: OUT = OFF. 
•  If (Y + Hysteresis) > X > Y, then: OUT = Previous State. 
Input 
X
 = Analog value. 
Y = Analog value 
Output 
OUT
 = Digital signal 
Block properties 
 
 
 
Double click on the function block to access the function block properties dialog box.