Function Blocks 
MDFL Mode Flag Function Block 
210    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
MDFL Mode Flag Function Block 
Description 
The MDFL label stands for Mode Flag. 
 
 
 
This block is part of the 
Loops category. 
 
Function 
Turns ON the output that corresponds to the current value of MODE. 
Turns OFF all other outputs. 
Input 
MODE
 = The MODE input must connect to the MODE output of a PID, CARB, TPSC, or ONOFF 
function block. 
Output 
REM = ON
  If MODE = Remote Setpoint 
LOCAL = ON  If MODE = Local Setpoint 
AUTO = ON  If MODE = Automatic Control 
MAN = ON   If MODE = Manual Control 
IMAN = ON   If MODE = Loop in Initialization Manual 
LO = ON  If MODE = Local Override 
Block properties 
Double click on the function block to access the function block properties dialog box.