Function Blocks
CAVG Continuous Average Function Block
118 HC900 Hybrid Control Designer Function Block Reference Guide Revision 11
2/07
Block properties
Double click on the function block to access the function block properties dialog box.
Configuration parameters
Table 37 Continuous average configuration parameters
Properties Group Parameter Index # Parameter Description Value or Selection
Set Avg. Period
Averaging
Period
0
Time period in which the Continuous
Average will be calculated.
When the averaging period elapses,
the last valid value will be set equal to
the instantaneous value.
The internal accumulators and sample
counters will be cleared and the time
remaining will be re-initialize to the full
average period.
0.1 to 1440.0 in
minutes