Function Blocks 
PID Function Block 
270    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
TRV = Output Track value in Percentage (PID Output = TRV Input when TRC = ON.) 
TRC = Output Track Command [ON, OFF] (On -Enables TRV.) (Mode = Local Override) 
BIAS = Remote Bias value for Ratio PID 
SWI = Switch Inputs (from SWO on LPSW function block) 
  0 = No Change 
  1 = Initiate Autotuning 
  2 = Change Control Action 
  4 = Force Bumpless Transfer 
  8 = Switch to Tune Set 1 
  16 = Switch to Tune Set 2 
MDRQI = External Mode request (typically connected to the MDRQO output of a MDSW function block 
that encoded discrete switch inputs). 
  0 = No Change 
  1 = Manual Mode Request 
  2 = Auto Mode Request 
  4 = Local Mode Request 
  8 = Remote Mode Request 
BCI = Back Calculation Input (for blocks used as Cascade Primary)—See ATTENTION 2. 
Outputs 
OUT = 
Control Output 
WSP = Working Setpoint in Engineering Units for monitoring 
AL1 = Alarm 1 - Digital Signal 
AL2 = Alarm 2 - Digital Signal 
DIRECT = ON = Direct; OFF = Reverse 
ATI = Autotune Indicator (ON = Autotune in Progress) 
MODE = Loop mode status (typically connected to the Mode Flags block for encoding). Value indicates  
modes as follows: 
 0.0 RSP AUTO 
 1.0 RSP MAN 
  2.0  RSP Initialization Manual (See ATTENTION 1) 
  3.0  RSP Local Override (See ATTENTION 1) 
 4.0 LSP AUTO 
 5.0 LSP MAN 
  6.0  LSP Initialization Manual (See ATTENTION 1) 
  7.0  LSP Local Override (See ATTENTION 1) 
BCO - Back Calculation Output (for blocks used as Cascade Secondary)—See ATTENTION 2.