Function Blocks 
PPO Position Proportional Output Function Block 
Revision 11    HC900 Hybrid Control Designer Function Block Reference Guide  295 
2/07     
REVERSE RELAY OUTPUT (Read Only) 
(This is configured automatically when Forward Relay Output is configured) 
Rack 
Address 
This is the address of the 
selected Rack.  
Same as Forward 
I/O Module 
Address 
Address of selected I/O 
module  
Same as Forward 
Channel 
Address 
Table 
continued 
2 
 
Channel on selected I/O 
Module 
Forward Channel +1 
Even number 2 thru 16.* 
FEEDBACK INPUT 
Rack 
Address 
This is the address of the 
selected Rack.  
1 to 5. 
I/O Module 
Address 
Address of selected I/O module   1 to 12 
Channel 
Address 
N/A 
 
Channel on selected I/O Module  1 to 16* 
*For HC900 controller’s 32 Channel DO Module, outputs 17 through 32 may not be used for TPO 
(Time Proportioning Output), PPO (Position Proportioning Output) or TPSC (Three Position Step 
Output) output types.