Function Blocks
AGA8DL Function Block
Revision 11 HC900 Hybrid Control Designer Function Block Reference Guide 19
2/07
Status
number
Block type Severity Description
14 AGA 8 - GROSS Error HEATING VALUE (HV) < 477.0 OR > 1211.0 BTU/FT^3
15 AGA 8 - GROSS Error GAS RELATIVE DENSITY (GRGR) < 0.55 OR > 0.870
MOLE FRACTION FOR N2 < 0.0 OR > 0.50
OR FOR CO2 < 0.0 OR > 0.30
OR FOR H2 < 0.0 OR > 0.10
16 AGA 8 - GROSS Error
OR FOR CO < 0.0 OR > 0.03
17 AGA 8 - GROSS Error REFERENCE TEMPERATURE < 32.0 OR > 77.O DEG F
18 AGA 8 - GROSS Error REFERENCE PRESSURE < 13.0 OR > 16.0 PSIA
22 AGA 8 - GROSS Warning FLOWING PRESSURE (PF) <=0.0 OR > 1200.0 PSIA
23 AGA 8 - GROSS Warning FLOWING TEMPERATURE (TF) < 32.0 OR > 130.0 DEG F
24 AGA 8 - GROSS Warning HEATING VALUE (HV) < 805.0 OR > 1208.0 BTU/FT^3
25 AGA 8 - GROSS Warning GAS RELATIVE DENSITY (GRGR) < 0.55 OR > 0.800
MOLE FRACTION FOR N2 < 0.0 OR > 0.20
OR FOR CO2 < 0.0 OR > 0.20
OR FOR H2 < 0.0 OR > 0.0
26 AGA 8 - GROSS Warning
OR FOR CO < 0.0 OR > 0.0
32 AGA 8 - DETAIL Error FLOWING PRESSURE (PF) < 0.0 OR > 40,000. PSIA
33 AGA 8 - DETAIL Error FLOWING TEMPERATURE (TF) < -200 OR > 760 DEG F
MOLE FRACTION FOR METHANE < 0.0 OR > 1.0
FOR NITROGEN < 0.0 OR > 1.0
FOR CARBON DIOXIDE < 0.0 OR > 1.0
FOR ETHANE < 0.0 OR > 1.0
FOR PROPANE < 0.0 OR > 0.12
FOR WATER < 0.0 OR > 0.10
FOR H2S < 0.0 OR > 1.0
FOR HYDROGEN < 0.0 OR > 1.0
FOR CARBON MONOXIDE < 0.0 OR > 0.03
FOR OXYGEN < 0.0 OR > 0.21
FOR BUTANES < 0.0 OR > 0.06
FOR PENTANES < 0.0 OR > 0.04
FOR HEXANES + < 0.0 OR > 0.10
FOR HELIUM < 0.0 OR > 0.03
36 AGA 8 - DETAIL Error
FOR ARGON < 0.0 OR > 1.0
37 AGA 8 - DETAIL Error REFERENCE TEMPERATURE < 32.0 OR > 77.0 DEG F
38 AGA 8 - DETAIL Error REFERENCE PRESSURE < 13.0 OR > 16.0 PSIA
39 AGA 8 - DETAIL Error SUM OF MOLE FRACTIONS < 0.98 OR > 1.020
42 AGA 8 - DETAIL Warning FLOWING PRESSURE (PF) < 0.0 OR > 1750. PSIA