Function Blocks 
SEQ Sequencer Function Block 
336    HC900 Hybrid Control Designer Function Block Reference Guide  Revision 11 
  2/07 
^RESET   = Pulse input for reset 
HOLD   = Input for Hold (level trigger) 
^RUN  = Edge triggered input for run 
^ADV  = Edge triggered input to advance to the next step defined in the current 
     sequence step 
 
 
ATTENTION 
If either or both NSEQ and NSTEP are connected directly to analog variables, when that 
analog variable changes (for example: via a recipe load), then the Sequencer block will 
immediately use the new value internally. 
If NSEQ or NSTEP is connected to any other function type then their values are loaded into 
the Sequencer only when ^SET goes through a positive transition. 
 
Outputs 
OUT1 thru OUT16
 = State Output values 
STMR  = Time remaining in current step (minutes) 
MODE  = Sequence Mode [N/A, RESET, RUN, HOLD, STOP] 
STATE = Current State number (Output states as configured by the user) 
AUX   = Auxiliary Output corresponding to the current step 
STEP  = Current Step number 
Configurable Parameters 
The Sequencer properties dialog box is divided into 3 tab cards 
General tab 
Parameter  Index #  Parameter Description  Value or Selection 
Tag Name 
0  Tag Name of Sequencer  16 characters maximum 
Descriptor 
  Description of Sequence  16 characters maximum 
Aux label 
 
Auxiliary Output label for OI 
Display 
8 characters maximum 
Aux Units 
 
Auxiliary Output Engineering 
Units for OI Display 
4 Characters maximum 
Aux Decimal 
Places 
 
Decimal Places for Auxiliary 
Output Value 
0-3 
 
Labels tab 
Parameter  Index #  Parameter Description  Value or Selection 
Out1 thru 
Out16 
0  Output Labels for OI Display  8 characters maximum