Function Blocks
TCPW Function Block
398 HC900 Hybrid Control Designer Function Block Reference Guide Revision 11
2/07
Sequence
Number
Parameter
Field
Action Selections Comments
3
Type in the address of
the register (in Hex) on
the slave device
4
From the drop down
menu, select the
Register Data Type
Float
Unsigned 32
Signed 32
Unsigned 16
Signed 16
Several standard
Modbus RTU function
codes are supported.
These standard
function codes provide
basic support for IEEE
32-bit floating point
numbers and 16-bit
integer register
representation of
instrument’s process
data. (see Sequence
Number 5 below)
5
The function code for
“Unsigned 16 or
Signed 16
register data
type is (06)*
The function code for
“Float, Unsigned 32 or
Signed 32
register data
type is (10 hex)*
*
automatically selected
when you select
“Register Data Type”
Preset Single
Registers –
Function Code
06
Preset Multiple
Registers –
Function Code
10 hex
Function code 06
presets integer value
into a single register.
Function Code 10 hex
presets values into
holding registers.
NOTE: Refer to the
Communications
manual for the function
codes supported by the
specific device.
6
You must press [APPLY] to accept the register changes.