Function Blocks 
AI Function Block 
Revision 11    HC900 Hybrid Control Designer Function Block Reference Guide  45 
2/07     
 
Failsafe rules 
If the controller is unable to access the physical channel or the sensor is faulty, and: 
 
•  If Failsafe is “Use Value”  Then OUT = Configured Failsafe value 
•  If Failsafe is enabled and downscale  Then OUT = Range Lo (linear) 
Low Range Value of input type (T/C and RTD) 
•  If Failsafe is enabled and upscale  Then OUT = Range Hi (linear) 
High Range Value of input type (T/C and RTD)