Function Blocks 
 
Revision 11    HC900 Hybrid Control Designer Function Block Reference Guide  83 
2/07     
Output Description 
ALMUNACK  Alarm unacknowledge is ON if any operator panel’s alarm is unacknowledged. 
HWOK  Hardware OK is ON if there are no faults. 
LOWBTRY  Low Battery is ON if the battery is low, Off when battery is good. 
HI TEMP  High CJ Temperature is ON if the CJ temperature is high. 
MSTR FAIL  Communications Failure is ON when Modbus master diagnostic is not good 
BAD BLOCK  Bad Block is ON when one or more blocks are not operating properly. 
LOCKED  On when Controller Mode switch is locked in the current mode by switch position. 
TIME OFF 
Number of seconds power was turned off. Valid for one cycle of control blocks execution following 
power up. Then it is cleared to zero. 
DS LIMIT 
ON when the configuration storage warning limit is exceeded. OFF when the storage capacity falls 
below the warning limit. 
RSV AVAIL 
C70R controllers only. ON when the Reserve CPU is available for failover. OFF when the Reserve 
CPU is unavailable for failover. 
On other controllers this pin is called “N/A” and serves no purpose other than a placeholder for 
RSV AVAIL. 
 Possible reasons: 
No Reserve CPU installed. 
Hardware failure is preventing database synchronization between the CPUs. 
Firmware mismatch between the CPUs.