No.: Day Time Nominal pressure
10
Tab. 65 User-defined timing program for nominal pressure change
When setting a timer program for the first time, note first the switching times on the "User-
defined time program" table for example.
In addition to individual weekdays, the controller has the following cycles:
■ Mon-Thu
■ Mon-Fri
■ Mon-Sat
■ Mon-Sun
■ Sat-Thu
Example
■ Base load period: Weekdays from 06:30AM–05:00PM, Fridays 06:30AM–03:00PM
■ Low load period: Midday from 12:00PM–01:00PM and remaining time
The timing program is established with the following switching points (maximum 10 switching
points available):
No.: Weekday Time Nominal pressure
01 Mon-Fri 06:30AM
pA on
02 Mon-Fri 12:00PM
pB on
03 Mon-Fri 01:00PM
pA on
04 Mon-Thu 05:00PM
pB on
05 Fri 03:00PM
pB on
Tab. 66 Example: Switching points, nominal pressure change
Deleting an existing timing program
Delete an existing timing program as follows:
Precondition Password access level 2 is activated.
1. Open the 5.2.3
<Configuration – Pressure control – Load control>
menu.
2. Use the «Up» or «Down» keys to select the
pA/pB Clock
line.
3. Press the «Enter» key.
The
Timing program
menu is displayed.
8 Initial Start-up
8.9 Setting the machine for local mode
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
115