For connecting the machines to a network (LAN) or switch:
Connect the Ethernet cable for each machine to the LAN connection or switch.
1. Attach the RJ45-plug to the cable end.
2. Plug the RJ45plug into the network socket until it latches.
8.10.4.2 Setting the controller of machine 1 as master
Precondition The electrical connection is made.
Password access level 2 is activated.
Setting the switching points pA and pB
1. Open the 5.2.2
<Configuration – Pressure control – Pressure settings>
menu.
The
pA
line is displayed.
2. Press «Enter».
The value for
pA
flashes.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.2.2 Pressure settings
Menu
Setpoint pressure
pA SP: 123psi ¦ SD: −7.3psi
Active line
pB SP: 119psi ¦ SD: −7.3psi
·········
System pressure low
< 72.5psi ¦ SD: 7.2psi
3. Use «Up» or «Down» to set the
pA
value.
4. Press «Enter».
The setting is applied.
5. Press «Down».
The
pB
line is displayed.
6. If necessary, adjust the value for the
pB
switching differential in the same manner.
Setting the times
The following options for load control are provided by SIGMA CONTROL 2 for selecting times:
1: Timer program
2: Timer
1. Select either one of the time settings (time program or timer) or base load sequencing.
2. Follow the instructions below for the settings required.
Alternative 1: Set timer program
Precondition The electrical connection is made.
Password access level 2 is activated.
Setting the set-point pressure change with a timer program; see chapter 8.9.2.
8 Initial Start-up
8.10 Configuring the machine for master control
134
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE