3. Press the «Up» key.
The check box is activated.
4. Press the «Enter» key.
The test mode is activated.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
9.1 Inspections
Menu
Safety valve : ☑
Active line with check box
pRV: 232psi ¦ pi ⇞ 36.0psi
Safety relief valve actuating pressure, internal pres‐
sure
Reset :
·········
ADT ⇞ : ☐
Offset 32°F ¦ ADT ⇞ 32.0°F
5.
Risk of hearing damage when safety relief valve blows off!
Close all maintenance doors, attach and secure all removable panels.
Always wear ear protection.
6.
Risk of burns due to released cooling oil and compressed air when safety relief
valve blows off!
Close all maintenance doors, attach and secure all removable panels.
Wear eye protection.
7. Perform the test as follows according to machine type.
9 Operation
9.13 Safety relief valve test
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
191

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet