Message Possible cause Remedy
0253 W
Oil cooler fan FC
Service mode active
Frequency converter in service mode. Exit service mode.
0254 W
Oil cooler fan FC
Service mode active
Frequency converter in service mode. Exit service mode.
0255 W
Oil-/air cooler fan FC
Service mode active
Frequency converter in service mode. Exit service mode.
0256 W
Air cooler fan FC
Service mode active
Frequency converter in service mode. Exit service mode.
0260 W
Oil-/air cooler fan FC
Alarm %d
Fan frequency converter faulty. Acknowledge message.
Contact an authorized KAES‐
ER service representative.
0261 W
Oil-/air cooler fan FC
Alarm %d
Fan frequency converter faulty. Acknowledge message.
Contact an authorized KAES‐
ER service representative.
0262 W
Oil cooler fan FC
alarm %d
Fan frequency converter faulty. Acknowledge message.
Contact an authorized KAES‐
ER service representative.
0263 W
Oil cooler fan FC
alarm %d
Fan frequency converter faulty. Acknowledge message.
Contact an authorized KAES‐
ER service representative.
0264 W
Air cooler fan FC
alarm %d
Fan frequency converter faulty. Acknowledge message.
Contact an authorized KAES‐
ER service representative.
0300 W
SD card write error
Write protection activated?
Memory card defective.
Deactivate write protection.
Use a new memory card.
0866 W
AII%d.0%d - error
power supply
Voltage supply for ext. sensor at ana‐
logue input faulty.
Check power supply.
0867 W
AII%d.0%d - overload
fault
Overload at analog input for ext. sensor. Contact an authorized KAES‐
ER service representative.
0868 W
AII%d.0%d - open
circuit
Wire break in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0869 W
AII%d.0%d - short-
circuit
Short circuit in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0872 W
AII%d.0%d - error
power supply
Voltage supply for ext. sensor at analog
input faulty.
Check power supply.