Message Possible cause Remedy
0873 W
AII%d.0%d - overload
fault
Overload at analog input for ext. sensor. Contact an authorized KAES‐
ER service representative.
0874 W
AII%d.0%d - open
circuit
Wire break in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0875 W
AII%d.0%d - short-
circuit
Short circuit in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0878 W
AII%d.0%d - error
power supply
Voltage supply for ext. sensor at ana‐
logue input faulty.
Check power supply.
0879 W
AII%d.0%d - overload
fault
Overload at analog input for ext. sensor. Contact an authorized KAES‐
ER service representative.
0880 W
AII%d.0%d - open
circuit
Wire break in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0881 W
AII%d.0%d - short-
circuit
Short circuit in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0884 W
AII%d.0%d - error
power supply
Power supply for ext. sensor at analog in‐
put faulty.
Check power supply.
0885 W
AII%d.0%d - overload
fault
Overload at analog input for ext. sensor. Contact an authorized KAES‐
ER service representative.
0886 W
AII%d.0%d - open
circuit
Wire break in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0887 W
AII%d.0%d - short-
circuit
Short circuit in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
0897 W
AIR%d.0%d - short-
circuit
Short circuit in line for indicated analog
input.
Check line path and sensor
connection.
0898 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
0899 W
AIR%d.0%d - sensor
fault
Sensor fault at indicated analog input. Check line path and sensor
connection.
0900 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
10 Fault Recognition and Rectification
10.3 Interpreting warning messages
214
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet