16.3.2 Basic seng and opons
16.3.2.1 Staon name and IP conguraon
The
staon name and the IP conguraon can be assigned via the IO-Controller. These set-
tings enable the IO-Controller to idenfy the inverter in the network and manage the data
exchange.
The staon name and the IP conguraon can also be assigned via the »EASY Starter«:
•
The staon name of the inverter must be entered with permissible characters according to
the PROFINET specicaon. 40x2381:004
•
Display of the currently used staon name: 40x2382:004
•
The IP conguraon comprises the assignments of:
•
IP address 0x2381:001
•
Subnet mask 0x2381:002
•
Gateway address 0x2381:003
•
Display of the currently used IP conguraon: 40x2382:001 ... 0x2382:003
Save the staon name and the IP conguraon in the inverter with mains failure
protecon in order that the inverter can be idened via Ethernet if the IO Con-
tr
oller is switched o. 0x2022:003
See: 4Saving the parameter sengs ^
36
An invalid staon name or the assignment of invalid combinaons of IP address,
subne
t mask and gateway address may prevent a connecon to PROFINET.
In case of impermissible sengs, the red LED "BUS ERR" is blinking and the
error message "PROFINET: stack inialisaon error [0x8192]" is displayed.
4LED status display ^ 363
Parameter
Address Name / seng range / [default seng] Info
0x2381:001 PROFINET sengs: IP address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Set IP address
•
A chang
ed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 = 1).
0x2381:002 PROFINET sengs: Subnet
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Set subnet mask
•
A changed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 = 1).
0x2381:003 PROFINET sengs: Gateway
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Set gateway address
•
A chang
ed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 = 1).
•
The gateway address is valid if the network address of the IP address
is idencal to the gateway address. In this case, no gateway funcon-
ality is used.
•
DHCP is not supported.
0x2381:004 PROFINET sengs: Staon name Set
staon name
•
A changed value will only be eecve aer the PROFINET communica-
on is restarted (0x2380 = 1).
0x2381:005 PROFINET sengs: I&M1 System designaon Input/output of the I&M1 system designaon
•
The de
fault seng is an empty string.
0x2381:006 PROFINET sengs: I&M1
Installaon site Input/output of the I&M1 locaon idencaon code
•
The default seng is an empty string.
0x2381:007 PROFINET sengs: I&M2 Installaon date Input/output of the I&M2 date of installaon
•
The de
fault seng is an empty string.
0x2381:008 PROFINET sengs: I&M3
addional informaon Input/output of the I&M3 addional informaon
•
The de
fault seng is an empty string.
0x2381:009 PROFINET sengs: I&M4 signature code
["000000000000000000000000000000000000000000
0000000000000000000000000000000000000000000
00000000000000000000000"]
Input/output of the I&M4 signature
•
The de
fault seng is an empty string.
Conguring the network
PR
OFINET
Basic seng and opons
358