5.4.2 Manual seng of the motor data
There are two opons to parameterise a motor.
1. Enter nameplate data
Enter the following motor data:
40x2C01:001 Number of pole pair
s
40x2C01:002 St
ator resistance
40x2C01:003 Stator leakage inductance
40x2C01:004 Ra
ted speed
40x2C01:005 Rated frequency
40x2C01:006 Rated power
40x2C01:007 Ra
ted voltage
40x2C01:008 Cosine phi
40x2C01:009
Insulaon class
40x6075 Rated motor current
When you touch the "Esmate" buon in the engineering tool, more parameters depending
on the motor are shown.
2. Enter data of the motor data sheet
The motor data and the parameters depending on the motor are entered. The parameters
menoned under 1. are the following:
40x2D4C:001 Thermal
me constant of the winding
40x2D4C:002 Thermal me constant - laminated core
40x2D4C:003
Inuence of winding
40x2D4C:004 Starng value
40x6067 Ra
ted motor torque
Addionally for ASM:
40x2C02:001 Rotor resistance
40x2C02:002 Mutual induct
ance
40x2C02:003 Magnesing current
Addionally for PSM:
40x2C03:001 EMF constant
40x2C03:002 R
esolver pole posion
40x2C03:003 Temperature coecient magnets (kTN)
40x2C03:004 Enc
oder pole posion
Aer the motor data has been parameterised via one of the two opons, the following moni-
toring and limit values are inialised with motor-dependent preset values by touching the
"Inialise" buon:
40x2D44:001 Overspeed monitoring threshold
40x2D46:001 Ov
ercurrent monitoring threshold
40x2D49:003 Motor temperature monitoring warning threshold
40x2D49:004 Mot
or temperature monitoring error threshold
40x6073 Maximum current
40x6075 Ra
ted motor current
Basic seng
Motor data
Manual seng of the motor data