7.3.3.3 External master values
The Virtual mas
ter control signals parameter can be used to switch over the master value
source when the controller is enabled. 40x5045:010 Bit 31
If bit 31 of the Virtual master control signals parameter is set to TRUE, the external master
value sources are deselected. The virtual master takes over the moon control and synchroni-
ses itself via the selected master value source.
Prole calculaon parameters:
Virtual master
acceleraon 40x5046:003
Virtual master deceleraon 40x5046:004
Virtual master jerk 40x5046:005
Clutch-in direcon virtual master 0x5046:030
Conguring the "Sync and Correcon" TA
Mas
ter value sources
Virtual master
113