19.20 Cascading (CAS)
This funcon allows for the synchronised shutdown of an enre drive network.
Precondions
•
As sour
ce for the cascading request, the SD-In4 input must be parameterised.
0x21240x2124, 4: SD-In4
•
As an acve input for the "Emergency stop" funcon and the input delay, a value ≤ 10 ms
mus
t be parameterised for SD-In4. Safe inputs
•
As execung stop funcon, the "Safe torque o (STO)" funcon must be parameterised.
Safe Emergency Stop (SSE) 0x28A3:001 ^ 400
•
As restart behaviour of the drive aer execung Safe Torque O (STO), "Acknowledged
restart" must be parameterised. 0x2892:0010x2892:001
•
The control of the SD-Out1 output via a parameterised safety bus must be inhibited. Safety
bus
The plausibility check rejects other sengs
unl the plausibility check is para-
meterised correctly.
•
If the c
ascading safety
funcon is used in connecon with special operaon, "SS2" must be
parameterised as stop funcon in the operaon mode selector (OMS).
The STO stop funcon will trigger the "Cascading" funcon. Acvaon by means
of the enable s
witch (ES) is not possible.
Descripon of the principle
SD-Out1
SD-In4
i950 #1 i950 #2
SD-In4
SD-Out1
i950 #n
SD-In4
SD-Out1
Fig. 83: CAS funcon
With 0x2125:0010x2125:001, the me period is shown, which elapses from switching the SD-
Out1 output to the OFF state to recording the OFF state at the SD-In4 input.
•
If
,
aer a stop, the me period "0 ms" is shown, another safety funcon has triggered the
stop via the cascade.
•
The me period is shown unl the next system acknowledgement takes place.
Acvaon of the funcon
The funcon is acvated by parameterisaon of the SD-In4 input as source for a cascading
request (0x21240x2124, 4: SD-In4).
Parameter
Address Name / seng range / [default seng] Info
0x2124 CAS: Quelle SD-In
•
Read only
0 Deacvated
4 SD-In4
0x2125:001 CAS: Cascading: CAS: Stop delay
•
Read only: x ms
Safety
funcons
Cascading (CAS)
440