13.5 Parameterisable motor funcons
13.5.1 DC braking
The control modes for asynchronous motors provide the opportunity to use the "DC‑br
aking"
funcon (DC-injecon braking) for braking. In this case, the motor control injects a DC current
the amplitude of which is adjustable.
Precondions
Using the "DC braking" funcon, the motor control injects a DC current, the amplitude of
which is adjustable in the 0x2B80 parameter. To this end, it is necessary that the current con-
trol is adapted to the corresponding motor. For seng and opmising the current controller,
see Current controller. ^ 267
Details
The funcon can be used as follows:
1.
"DC braking" can be parameterised via bit 6 in the Lenze control word 0x2830.
In this case, the motor system itself can be used as an energy converter.
This opon is useful if
•
the system is not provided with a brake resistor required for absorbing the braking
energy. This method requires that a sucient braking torque can be achieved with "DC
braking".
•
the power of the brake chopper to be transformed is limited and thus must be exclu-
sively used for the main drives of the DC network. The quality of the deceleraon ramp
via "DC braking" is sucient for auxiliary drives and unburdens the brake chopper.
•
a fan drive is to be braked in the V/f characterisc operaon.
2.
"DC br
aking" can be parameterised as a response to minor faults.
An example of a minor fault is the error of an encoder of an asynchronous machine. Due to
the error, the quick stop funcon cannot be executed anymore. An
alternave is provided
by the guided shutdown with a minor deceleraon via the "DC braking" funcon.
Parameter
Address Name / seng range / [default seng] Info
0x2B80 Current for DC-injecon braking
0.00 ... [0.00] ... 500.00 A
Braking current for DC-injecon braking
Conguring the motor control
P
arameterisable motor funcons
DC braking
251