11.1 Basic seng
1.
Se
t the manufacturer spanning operang mode " Cyclic sync torque mode [10]" according
t
o CiA402.
A detailed descripon of this operang mode can be found in the "Operang mode
"CiA 402 Cyclic sync torque mode (cst)"" secon. ^ 191
2.
Set the rated motor torque. 40x6076
3.
Set the permissible maximum torque. 40x6072
The maximum torque is preset in 0x6072.
The change of the posive and negave limit of the maximum torque is described in
the "Torque limits" secon. ^ 189
4.
Parameterise speed limit. 0x2946
The maximum speed is preset. 40x6080
The change of the upper and lower speed limit is described in the "Speed limitaon"
secon. ^ 190
5.
Dene a torque setpoint for the torque control instead of a speed setpoint. The value is
giv
en in percent and based on the rated motor torque set in 0x6076.
The torque control with speed limitaon is now acve and the inverter responds to the
dened torque setpoint.
Conguring the torque control
Basic seng
188