Address Name / seng range / [default seng] Info
0x2550:008 Brake resistor: Warning threshold
50.0 ... [90.0] ... 150.0
%
Warning threshold for brake resistor monitoring.
•
If the ulisaon shown in reaches the threshold set, the response
selected in 0x2550:010 is eected.
•
The w
arning is reset with a hysteresis of 20 %.
0x2550:010 Brake resistor: Response to warning Selecon of the response that is executed when the warning threshold
f
or brake resistor monitoring is reached.
0 No response
1 Fault > CiA402
2 Warning
0x2550:011 Brake resistor: Response to error Selecon of the response to be executed when the error threshold for
brake resistor monitoring is reached.
Associated error code:
•
65282 | 0xFF02 - Brake resistor: overload fault
0 No response
1 Fault > CiA402
2 Warning
18.2 Manual jog parameters
P
arameter
Address Name / seng range / [default seng] Info
0x2836:001 Manual control mode: Current setpoint
0 ... [30] ... 200 %
Seng of the current setpoint value for manual control.
•
100 %
≡ Rated current ()
0x2836:002 Manual control mode: Frequency
-1000.0 ... [0.0] ... 1000.0 Hz
Seng of the frequency for manual control.
0x2836:003 Manual control mode: Ramp me (current)
0 ... [0] ... 1000 ms
Seng of the period of me during which the current setpoint value is
achieved from zero onwards.
0x2836:004 Manual control mode: Ramp me (frequency)
0 ... [500] ... 10000 ms
Seng of the period of me during which the frequency is achieved
from zero onwards.
The frequency ramp only starts up when the current ramp has reached
the value congured in 0x2836:001 (Current setpoint).
0x2836:005 Manual control mode: Time monitoring (frequency)
0 ... [2500] ... 100000 ms
Seng of the me period for me monitoring.
•
The manual control features a me monitoring funcon which is cou-
pled to a write access to 0x2836:002 (Frequency).
•
If no write access to 0x2836:002 takes place within the me period
set here, the frequency is moved to zero via the parameterised ramp.
When the 0 Hz have been reached, the inverter changes to the error
status and is inhibited. Aer acknowledging the error, the CiA402
state machine must be switched from "Switch-on inhibited" back to
the "Operaon enabled" state before proceeding with manual con-
trol.
0x2836:006 Manual control mode: Current controller gain
0.00 ... [20.00] ... 750.00 V/A
Seng of the current controller gain.
0x2836:007 Manual control mode: Current controller reset me
0.01 ... [20.00] ... 2000.00 ms
Seng of the current controller reset me.
Addional
funcons
Manual jog parameters
386