Address Name / seng range / [default seng] Info
0x2550:008 Brake resistor: Warning threshold
50.0 ... [90.0] ... 150.0
%
Warning threshold for brake resistor monitoring.
If the ulisaon shown in reaches the threshold set, the response
selected in 0x2550:010 is eected.
The w
arning is reset with a hysteresis of 20 %.
0x2550:010 Brake resistor: Response to warning Selecon of the response that is executed when the warning threshold
f
or brake resistor monitoring is reached.
0 No response
1 Fault > CiA402
2 Warning
0x2550:011 Brake resistor: Response to error Selecon of the response to be executed when the error threshold for
brake resistor monitoring is reached.
Associated error code:
65282 | 0xFF02 - Brake resistor: overload fault
0 No response
1 Fault > CiA402
2 Warning
18.2 Manual jog parameters
P
arameter
Address Name / seng range / [default seng] Info
0x2836:001 Manual control mode: Current setpoint
0 ... [30] ... 200 %
Seng of the current setpoint value for manual control.
100 %
≡ Rated current ()
0x2836:002 Manual control mode: Frequency
-1000.0 ... [0.0] ... 1000.0 Hz
Seng of the frequency for manual control.
0x2836:003 Manual control mode: Ramp me (current)
0 ... [0] ... 1000 ms
Seng of the period of me during which the current setpoint value is
achieved from zero onwards.
0x2836:004 Manual control mode: Ramp me (frequency)
0 ... [500] ... 10000 ms
Seng of the period of me during which the frequency is achieved
from zero onwards.
The frequency ramp only starts up when the current ramp has reached
the value congured in 0x2836:001 (Current setpoint).
0x2836:005 Manual control mode: Time monitoring (frequency)
0 ... [2500] ... 100000 ms
Seng of the me period for me monitoring.
The manual control features a me monitoring funcon which is cou-
pled to a write access to 0x2836:002 (Frequency).
If no write access to 0x2836:002 takes place within the me period
set here, the frequency is moved to zero via the parameterised ramp.
When the 0 Hz have been reached, the inverter changes to the error
status and is inhibited. Aer acknowledging the error, the CiA402
state machine must be switched from "Switch-on inhibited" back to
the "Operaon enabled" state before proceeding with manual con-
trol.
0x2836:006 Manual control mode: Current controller gain
0.00 ... [20.00] ... 750.00 V/A
Seng of the current controller gain.
0x2836:007 Manual control mode: Current controller reset me
0.01 ... [20.00] ... 2000.00 ms
Seng of the current controller reset me.
Addional
funcons
Manual jog parameters
386