Inverters I95AE322F I95AE330F I95AE345F I95AE355F I95AE375F I95AE390F I95AE411F
Rated power kW 22 30 45 55 75 90 110
Rated power hp 30 40 60 75 100 125 150
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-480 V
Rated mains current
without mains choke A 47.4 - - - - - -
with mains choke A 35.3 45.7 66.7 83 113 146 168
Apparent output power kVA 32 41 60 75 100 121 142
Rated output current
2 kHz A 40.4 52 77 96 124 156 180
4 kHz A 40.4 52 77 96 124 156 180
8 kHz A 40.4 52 77 96 124 140 162
16 kHz A 26.9 34.6 51.3 66.8 78.5 85.8 90
Power loss
2 kHz W 505 653 934 1151 1553 1855 2177
4 kHz W 536 694 994 1224 1654 1975 2319
8 kHz W 694 898 1292 1593 2157 2326 2731
16 kHz W 694 898 1292 1593 2157 2326 2731
at inverter disable W 32 39 39 44 44 44 44
Cyclic mains switching 3 mes per minute 1 me per minute
Max. motor cable length shielded
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20 20 20 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35 35 35 100 100 100 100
without EMC category m 100 100 100 200 200 200 200
Weight kg 10.7 16.7 16.7 24 24 35.6 35.6
Weight lb 23.6 37 37 53 53 78.5 78.5
Technical data
3-phase mains connecon 480 V
Ra
ted data
461