3) Analog Input Module (A/D conversion module)
For the analog input module supported by XG-SIM, refer to the following table.
Module name Support
XGF-AV8A (Voltage type 8ch) ○
XGF-AC8A (Current type 8ch) ○
XGF-AD4S (Insulation type 4ch)
Ⅹ
XG-SIM supports 4 types of input voltage ranges and digital data formats and 2 kinds of input current ranges as follows.
Input voltage range Input current range Digital output format
1 ~ 5V 4 ~ 20mA 0 ~ 16000
0 ~ 5V 0 ~ 20mA -8000 ~ 8000
0 ~ 10V - 1000 ~ 5000
-10 ~ 10V - 0 ~ 10000 (%)
XG-SIM supports the following analog input parameters.
Parameter Support Parameter Support
Operation channel ○ Filter constant ○
Input voltage(current) range ○ Averaging ○
Output data type ○ Averaging method ○
Filter process
Ⅹ
Average ○
Analog input may be directly set in XG-SIM window and the input range is valid only within the input voltage(current) range set in the
parameter.
Notes
- For the details on the parameters of analog input module and the programming, refer to the manual of a module.