Chapter 18 Dedicated XGR Function
18-13
5. Click [Finished], when Changing Base is finished.
[Dialog box]
[Description of dialog box]
a. Information: Information of Changing Base Finished
b. Back: It is inactive mode after base is removed.
c. Finish: Finish Base Changing Wizard
Notes
Please follow below step when base changing without Base Changing Wizard.
[Step]
1. Set [I/O Skip] setting to change on base. .
2. Set Fault Mask on base.
3. Remove the base from PLC.
4. Install the base to change.
5. Release [I/O Skip] setting on corresponding base.
6. Selects [Online] – [PLC Errors/Warnings], Check the error in base.
7. Selects [Online] – [I/O Information], Check the module is installed normally.
8. If there is no error, release the Fault Mask on corresponding base.
Please refer to XGR CPU User’s Manual for additional explanation.
a
b
c