Table of Functions
315
Code
Comm.
Address
Name
LCD Display
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
gradient
06
14
0h1306
S-curve
deceleration
end point
gradient
Dec S End
1-100(%)
40
X/A
O
I/P
p.130
07
0h1307
Start Mode
Start Mode
0
Acc
0:Acc
X/A
O
I/P
p.138
1
DC-Start
08
15
0h1308
Stop Mode
Stop Mode
0
Dec
0:Dec
X/A
O
I/P
p.139
1
DC-Brake
2
Free-Run
4
Power
Braking
09
0h1309
Selection of
prohibited
rotation
direction
Run Prevent
0
None
0:
None
X/A
O
I/P
p.122
1
Forward
Prev
2
Reverse
Prev
10
0h130A
Starting with
power on
Power-on
Run
0
No
0:No
O/A
O
I/P
p.123
1
Yes
12
16
0h130C
DC braking
time at
startup
DC-Start
Time
0.00-60.00(s)
0.00
X/A
O
I/P
p.138
13
0h130D
Amount of
applied DC
DC Inj Level
0-200(%)
50
X/A
O
I/P
p.138
14
17
0h130E
Output
blocking time
before DC
braking
DC-Block
Time
0.00- 60.00(s)
0.10
X/A
O
I/P
p.139
15
17
0h130F
DC braking
time
DC-Brake
Time
0.00- 60.00(s)
1.00
X/A
O
I/P
p.139
16
17
0h1310
DC braking
rate
DC-Brake
Level
0-200(%)
50
X/A
O
I/P
p.139
17
17
0h1311
DC braking
frequency
DC-Brake
Freq
Start frequency-
60Hz
5.00
X/A
O
I/P
p.139
20
0h1314
Dwell
frequency on
acceleration
Acc Dwell
Freq
Start frequency-
Maximum
frequency(Hz)
5.00
X/A
O
I/P
p.172
15
DC braking and power braking (Ad.08, stop mode options 1 and 4) are not available
when dr.09 (Control Mode) is set to 6 (PM Sensorless).
16
Displayed when Ad. 07 is set to 1 (DC-Start).
17
Displayed when Ad. 08 is set to 1 (DC-Brake).