Table of Functions
346
Code
Comm.
Address
Name
LCD Display
Setting Range
Initial
Value
Property*
V/
F
SL
Ref.
06
0h1B06
Input voltage
range during
open-phase
IPO V Band
1-100(V)
15
X/A
O
I/P
p.257
07
0h1B07
Deceleration
time at fault
trip
Trip Dec
Time
0.0-600.0(s)
3.0
O/A
O
I/P
-
08
0h1B08
Selection of
startup on trip
reset
RST Restart
0
No
0:No
O/A
O
I/P
p.214
1
Yes
09
0h1B09
Number of
automatic
restarts
Retry
Number
0-10
0
O/A
O
I/P
p.214
10
63
0h1B0A
Automatic
restart
delay time
Retry Delay
0.0-60.0(s)
1.0
O/A
O
I/P
p.214
12
0h1B0C
Motion
at speed
command
loss
Lost Cmd
Mode
0
None
0:None
O/A
O
I/P
p.259
1
Free-Run
2
Dec
3
Hold Input
4
Hold Output
5
Lost Preset
13
64
0h1B0D
Time to
decide
speed
command
loss
Lost Cmd
Time
0.1-120(s)
1.0
O/A
O
I/P
p.259
14
64
0h1B0E
Operation
frequency
at speed
command
loss
Lost Preset
F
Start
frequency-
Maximum
frequency(Hz)
0.00
O/A
O
I/P
p.259
15
64
0h1B0F
Analog input
loss decision
level
AI Lost
Level
0
Half x1
0:Half of
x1
O/A
O
I/P
p.259
1
Below x1
17
0h1B11
Overload
OL Warn
0
No
0:No
O/A
O
I/P
p.251
63