398
Technical Specification
3 Phase 200V (0.4-4 kW)
Model
□□□□
S1002
□□□□
0004
0008
0015
0022
0037
0040
Applied
motor
Heavy load
HP
0.5
1.0
2.0
3.0
5.0
5.4
kW
0.4
0.75
1.5
2.2
3.7
4.0
Normal load
HP
1.0
2.0
3.0
5.0
5.4
7.5
kW
0.75
1.5
2.2
3.7
4.0
5.5
Rated
output
Rated apacity
(kVA)
Heavy
load
1.0
1.9
3.0
4.2
6.1
6.5
Normal
load
1.2
2.3
3.8
4.6
6.9
6.9
Rated current
[3-Phase
input] (A)
Heavy
load
2.5
5.0
8.0
11.0
16.0
17.0
Normal
load
3.1
6.0
9.6
12.0
18.0
18.0
Rated current
[Single-Phase
input] (A)
Heavy
load
1.5
2.8
4.6
6.1
8.8
9.3
Normal
load
1.8
3.3
5.7
6.6
9.9
9.9
Output frequency
0-400 Hz (IM Sensorless: 0-120 Hz)
Output voltage (V)
3-phase 200-240 V
Rated
input
Working voltage (V)
3-phase 200-240 VAC (-15% to +10%)
Single phase 240VAC(-5% to +10%)
Input frequency
50-60 Hz (5%)
(In case of single phase input, input frequency is only
60Hz(5%).)
Rated current
(A)
Heavy
load
2.2
4.9
8.4
11.8
17.5
18.5
Normal
load
3.0
6.3
10.8
13.1
19.4
19.4
Weight (lb /kg)
2/0.9
2/0.9
2.86/1.3
3.3/1.5
4.4/2.0
4.4/2.0
The standard motor capacity is based on a standard 4-pole motor.
The standard used for 200 V inverters is based on a 220 V supply voltage, and for
400V inverters is based on a 440 V supply voltage.
The rated output current is limited based on the carrier frequency set at Cn.04.
The output voltage becomes 20~40% lower during no-load operations to protect the
inverter from the impact of the motor closing and opening (0.4-4.0kW models only).
IP66 models do not support normal load operation.