Technical Specification
399
3 Phase 200V (5.5-15 kW)
Model
□□□□
S1002
□□□□
0055
0075
0110
0150
Applied
motor
Heavy load
HP
7.5
10
15
20
kW
5.5
7.5
11
15
Normal load
HP
10
15
20
25
kW
7.5
11
15
18.5
Rated
output
Rated
capacity
(kVA)
Heavy
load
9.1
12.2
17.5
22.9
Normal
load
11.4
15.2
21.3
26.3
Rated
current [3-
Phase input]
(A)
Heavy
load
24.0
32.0
46.0
60.0
Normal
load
30.0
40.0
56.0
69.0
Rated
current
[Single-
Phase input]
(A)
Heavy
load
13.0
18.0
26.0
33.0
Normal
load
16.0
22.0
31.0
38.0
Output frequency
0-400 Hz (IM Sensorless : 0-120 Hz)
Output voltage (V)
3 phase 200-240V
Rated
input
Working voltage (V)
3 phase 200-240VAC (-15% to +10%)
Single phase 240VAC(-5% to +10%)
Input frequency
50-60 Hz (5%)
(In case of single phase input, input frequency is only
60Hz(5%).)
Rated
current (A)
Heavy
load
25.8
34.9
50.8
66.7
Normal
load
32.7
44.2
62.3
77.2
Weight (lb /kg)
(Built-in EMC filter)
7.3/3.3
(6.8/3.1)
7.3/3.3
(6.8/3.1)
10/4.6
(9.7/4.4)
16/7.1
(15.2/6.9)
The standard motor capacity is based on a standard 4-pole motor
The standard used for 200 V inverters is based on a 220 V supply voltage, and for
400V inverters is based on a 440 V supply voltage.
The rated output current is limited based on the carrier frequency set at Cn.04.
IP66 models do not support normal load operation.