• IP66(NEMA 4X Indoor Only)
• 0.4-22kW: Keypad (LCD loader: Installation available
but sold separately.)
Heavy load: -10-50℃ (14–122F), normal load: -10-40℃
(14–104F)
No ice or frost should be present.
Working under normal load at 50℃ (122F), it is
recommended that less than 80% load is applied.
Relative humidity less than 90% RH (to avoid condensation
forming)
Prevent contact with corrosive gases, inflammable gases,
oil stains, dust, and other pollutants (Pollution Degree 3
Environment).
Maximum 1000m above sea level for standard operation.
From 1000 to 4000m, the rated input voltage and rated
output current of the drive must be derated by 1% for every
100m. / less than 1G (9.8m/sec
2
)
* , ** IP66 models do not support normal load operation.