7 APPLICATION INSTRUCTIONS
7.27 Module Access Instructions
1063
7
Reading the module model name
TYPERD(P)
These instructions read the module name of the specified slot.
■Execution condition
■Description, range, data type
■Applicable devices
Ladder ST
ENO:=TYPERD(EN,H,d);
ENO:=TYPERDP(EN,H,d);
FBD/LD
Instruction Execution condition
TYPERD
TYPERDP
Operand Description Range Data type Data type (label)
(H) Start I/O number (first three digits in four-digit hexadecimal
representation) of a model read target module
0H to FFH, 3E0H to
3E3H
16-bit unsigned binary ANY16
(d) (d)+0: Instruction execution result
(d)+1 to (d)+9: Module name
Word ANY16_ARRAY
(Number of elements:
10)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(H)
(d)
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)