1530
15 NETWORK COMMON INSTRUCTIONS
15.2 CC-Link Dedicated Instructions
Writing data to the target station
J(P).RIWT, G(P).RIWT
These instructions write the specified number of points of data to a device of the target station.
■Execution condition
■Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Ladder ST
ENO:=J_RIWT(EN,J,s1,s2,d);
ENO:=JP_RIWT(EN,J,s1,s2,d);
ENO:=G_RIWT(EN,U,s1,s2,d);
ENO:=GP_RIWT(EN,U,s1,s2,d);
FBD/LD
Instruction Execution condition
J.RIWT
G.RIWT
JP.RIWT
GP.RIWT
Operand Description Range Data type Data type (label)
(J/U) J(P).RIWT (J): Own station network number 1 to 239 16-bit unsigned binary ANY16
G(P).RIWT (U): Start I/O number (first three digits in four-
digit hexadecimal representation) of own station
or own node
00H to FEH 16-bit unsigned binary ANY16
(s1) Own station start device where control data is
stored
Refer to the control data. Device name ANY16
*1
(s2) Own station start device for storing written data Device name ANY16
*1
(d) Device of the own station, which turns on for one
scan upon completion of the instruction.
When the instruction completes with an error,
(d)+1 also turns on.
Bit ANYBIT_ARRAY
(Number of elements: 2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)