11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
Manual output
S.MOUT
This instruction reads the manipulated value (MV) from the loop tag memory and performs output conversion.
Execution condition
Setting data
Description, range, data type
Applicable devices
Block memory
Ladder ST
ENO:=S_MOUT2(EN,s1,s2,d1,d2);
FBD/LD
Instruction Execution condition
S.MOUT
Operand Description Range Data type
(s1) Empty string specification
(Specify "" in ladder. Specify '' in ST or FBD/LD.)
String
(d1) Block memory start device Refer to "Block memory". Single-precision real
number
(s2) Operation constant start device Refer to "Operation constant". Word
(d2) Loop tag memory start device Refer to "Loop tag memory". Word
EN Execution condition Bit
ENO Execution result Bit
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, R, ZR,
RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s1) 
(d1) 
(s2)  
(d2) 
Operand: (d1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 Single-precision
real number
System
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s1) (d1) (s2) (d2)
EN ENO
d1
d2
s1
s2