1554
16 ETHERNET INSTRUCTIONS
16.3 Fixed Buffer Communications Instructions
16.3 Fixed Buffer Communications Instructions
Reading receive data
GP.BUFRCV, ZP.BUFRCV
These instructions read receive data from the external device through fixed buffer communications
■Execution condition
■Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Ladder ST
ENO:=GP_BUFRCV(EN,U,s1,s2,d1,d2);
ENO:=ZP_BUFRCV(EN,U,s1,s2,d1,d2);
FBD/LD
Instruction Execution condition
GP.BUFRCV
ZP.BUFRCV
Operand Description Range Data type Data type (label)
(U) GP.BUFRCV Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own
node
00H to FEH 16-bit unsigned binary ANY16
ZP.BUFRCV Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own
node
00H to FEH String ANY16_OR_STRING_
SINGLE
(s1) Connection No. 1 to 16 16-bit unsigned binary ANY16
(s2) Start device of the own station where control data is
stored
Refer to the control data. Device name ANY16
*1
(d1) Own station start device for storing the receive data Device name ANY16
*1
(d2) Device of the own station, which turns on for one
scan upon completion of the instruction.
When the instruction completes with an error, (d2)+1
also turns on.
Bit ANYBIT_ARRAY
(Number of elements: 2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)