19 CC-LINK INSTRUCTIONS
19.7 Setting Network Parameters
1661
19
19.7 Setting Network Parameters
G(P).RLPASET
These instructions set network parameters in the master station and starts up the data link.
■Execution condition
■Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
*2 If this operand is omitted, specify the dummy device or label.
Ladder ST
ENO:=G_RLPASET(EN,U,s1,s2,s3,s4,s5,d);
ENO:=GP_RLPASET(EN,U,s1,s2,s3,s4,s5,d);
FBD/LD
Instruction Execution condition
G.RLPASET
GP.RLPASET
Operand Description Range Data type Data type (label)
(U) Start I/O number (first three digits in four-digit
hexadecimal representation) of a module
00H to FEH 16-bit unsigned binary ANY16
(s1) Start device where control data is stored Refer to the control data. Device name ANY16
*1
(s2)
*2
Start device containing the slave station setting data Device name ANY16
*1
(s3)
*2
Start device containing the reserved station specification
data
Device name ANY16
*1
(s4)
*2
Start device containing the error invalid station
specification data
Device name ANY16
*1
(s5)
*2
Start device containing the automatic update buffer
assignment data
Device name ANY16
*1
(d) Device that turns on for one scan upon completion of the
instruction
When the instruction completes with an error, (d)+1 also
turns on.
Bit ANYBIT_ARRAY
(Number of elements: 2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(U) (s1) (s2) (s3) (s4) (s5) (d)