280
6 BASIC INSTRUCTIONS
6.2 Arithmetic Operation Instructions
Dividing BCD 8-digit data
DB/(P)
These instructions perform division between the two sets of BCD 8-digit data specified.
Execution condition
Setting data
Description, range, data type
Applicable devices
Ladder ST
Not supported
FBD/LD
( is to be replaced by either of the following: DBDIVISION, DBDIVISIONP.)
Instruction Execution condition
DB/
DB/P
Operand Description Range Data type Data type (label)
(s1) Dividend data or the start device where dividend data is
stored
0 to 99999999 BCD 8-digit ANY32
(s2) Divisor data or the start device where divisor data is stored 0 to 99999999 BCD 8-digit ANY32
(d) Start device for storing the operation result BCD 16-digit ANY32_ARRAY
(Number of elements:
2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s1) 
(s2) 
(d)  
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s1) (s2) (d)
EN ENO
ds1
s2

Table of Contents