6 BASIC INSTRUCTIONS
6.7 Data Transfer Instructions
525
6
Transferring n-bit data
BLKMOVB(P)
These instructions batch-transfer the (n) points of bit data.
Execution condition
Setting data
Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Applicable devices
Ladder ST
ENO:=BLKMOVB(EN,s,n,d);
ENO:=BLKMOVBP(EN,s,n,d);
FBD/LD
Instruction Execution condition
BLKMOVB
BLKMOVBP
Operand Description Range Data type Data type (label)
(s) Transfer source block data Bit ANY_BOOL
*1
(d) Transfer destination block data Bit ANY_BOOL
*1
(n) Number of transfer data points 0 to 65535 16-bit unsigned binary ANY16
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s) 
(d)  
(n)  
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s) (d) (n)
EN ENO
sd
n