EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Converting REAL to DINT

Mitsubishi Electric MELSEC iQ-R Series
2110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25 TYPE CONVERSION FUNCTIONS
25.41 Converting REAL to DINT
1847
25
25.41 Converting REAL to DINT
REAL_TO_DINT(_E)
These functions convert a value from REAL data type to DINT data type.
Setting data
Description, type, data type
Processing details
Operation processing
These functions convert the value input to (s) from REAL data type to DINT data type, and output the converted value from
(d).
Input a REAL data type value to (s) within the range of -2147483648 to 2147483647.
After conversion, the first digit after the decimal point of the input value (REAL data type) is rounded off.
Operation result
1. Function without EN/ENO
The operation processing is performed. The operation result is output from (d).
2. Function with EN/ENO
The execution conditions and operation results will be as follows.
*1 If the value FALSE is output from ENO, the output data from (d) will be undefined. Create a program so that the undefined value will not
be used in operations.
Ladder, FBD/LD Structured text
[Without EN/ENO] [With EN/ENO] [Without EN/ENO]
d:=REAL_TO_DINT(s);
[With EN/ENO]
d:=REAL_TO_DINT_E(EN,ENO,s);
Argument Description Type Data type
EN Execution condition (TRUE: Executed, FALSE: Not executed) Input variable BOOL
s (IN) Input Input variable REAL
ENO Output status (TRUE: Normal, FALSE: Abnormal) Output variable BOOL
d Output Output variable DINT
Execution condition Operation result
EN ENO (d)
TRUE (executed) TRUE Operation result output value
FALSE (not executed) FALSE
*1
Undefined value
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
sd
EN ENO
ds
(s)
(d)
1654352116543521.0
DINTREAL

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R Series