1 OVERVIEW
1.5 Precautions on Programming
57
1
Operation when a long timer or long retentive timer device is
used
When the data to be handled exceeds the width (32 bits) of the current value, the long timer or long retentive timer operates
by using not only the area of the current value but also the areas of the previous value, contact, and coil.
When the BMOV instruction is used to batch-transfer current values, current values alone cannot be batch-transferred. Batch-
transfer the current values, contacts, and coils altogether and, after the batch transfer is finished, use only the current values.
When the DMOV instruction is used to batch-transfer current values, repeat the transfer of the current values alone using the
FOR to NEXT instruction.
To batch-transfer the current values of the timer device
When the BMOV instruction is used, only current values are batch-transferred.
Device Configuration
Timer (T)
Retentive timer (ST)
Counter (C)
Long timer (LT)
Long retentive timer (LST)
Long counter (LC)
T0 T0
T0
T2
T1
Current value
Current value
Contact Coil
LT0
LT1
Contact Coil
Contact Coil
Current value
FRT previous value
Current value
FRT previous value
LC0
LC1
LC0 LC0
Current value
Current value
Contact Coil
T0
T1
T2
T3
D0
D1
D2
D3
K4T0BMOVP D0
M0
Current value
Current value
Current value
Current value