7 APPLICATION INSTRUCTIONS
7.25 Clock Instructions
1023
7
Outputting a band comparison result of time data
TZCP(P)
These instructions compare the band between the time data of lower limit value (s1) and the time data of upper limit value (s2)
with the time data (s3) to be compared, and according to the comparison result (below, within zone, or above), (d), (d)+1, or
(d)+2 is turned on.
Execution condition
Setting data
Description, range, data type
Applicable devices
*1 T, ST, and C cannot be used.
The RnCPU and RnENCPU with firmware version "17" or later support these instructions. (Use an engineering tool with version "1.020W" or later.)
Ladder ST
ENO:=TZCP(EN,s1,s2,s3,d);
ENO:=TZCPP(EN,s1,s2,s3,d);
FBD/LD
Instruction Execution condition
TZCP
TZCPP
Operand Description Range Data type Data type (label)
(s1) Start device for storing the lower limit value of the time data
(hour, minute, second) to be compared
Refer to the function
details.
16-bit signed binary ANY16_ARRAY
(Number of elements: 3)
(s2) Start device for storing the upper limit value of the time data
(hour, minute, second) to be compared
Refer to the function
details.
16-bit signed binary ANY16_ARRAY
(Number of elements: 3)
(s3) Start device for storing the time data (hour, minute, second)
to be compared
Refer to the function
details.
16-bit signed binary ANY16_ARRAY
(Number of elements: 3)
(d) The start device where the comparison result is stored Bit ANYBIT_ARRAY
(Number of elements: 3)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s1)  
(s2)  
(s3)  
(d) 
*1
 
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s1) (s2) (s3) (d)
EN ENO
ds1
s2
s3